Trafag Mechanical Thermostats
HVAC MINISTAT FOR DUCTS MSK...
duct temperature controller internal set-point adjustment
Data sheet H72177
Instruction H73624
Set-point adjustment |
internal |
Sensor technology |
capillary tube, direct mounted sensor |
Sensor material |
Cu |
Protection |
IP54 |
Output |
micro switch |
Electrical connection |
terminal screw |
Operating temperature [°C] |
-30...+70 |
EN 60730-2-6 |
Type 2.B.H. |
Type |
Range T
[°C] |
Switching diff.
Adjustable
[°C] |
Media
Temperature
[°C] |
MSK |
30 |
0.....35 |
0.7...10 |
max.50 |
MSK |
40 |
-30....40 |
0.7..10 |
max.45 |
MSK |
80 |
10....80 |
0.7...10 |
max.100 |
MINISTAT FOR DIRECT MOUNTING MST...
internal set-point adjustment
incl. protection tube
Data sheet H72174
Instruction H736624
Set-point adjustment |
internal |
Sensor technology |
capillary tube, direct mounted sensor |
Sensor material |
Cu |
Protection |
IP54 |
Output |
micro switch |
Electrical connection |
terminal screw |
Operating temperature [°C] |
-30...+70 |
EN 60730-2-6 |
Type 2.B.H. |
Type |
Range T
[°C] |
Length G
[mm] |
Switching diff.
Adjustable
[°C] |
Media
Temperature
[°C] |
MST |
8015 |
-10.....80 |
150 |
2...12 |
max.105 |
MST |
8040 |
-10....80 |
400 |
2...12 |
max.85 |
MST |
9511 |
5....95 |
110 |
2...12 |
max.85 |
MST |
9515 |
5....95 |
150 |
2...12 |
max.105 |
MST |
9540 |
5....95 |
400 |
2...12 |
max.105 |
MST1 |
5015 |
20...150 |
150 |
2.5..16 |
max.165 |
MST1 |
5040 |
20...150 |
400 |
2.5..16 |
max.165 |