All Products
Ex Instruments  KTSB Trafag

Trafag Ex Instruments

KTSB High current ratings 16 A with mechanical reset
Stock
-3
Code
KTSB

Trafag Ex Instruments

SAFETY TEMPERATURE LIMITER KTSB

High current ratings 16 A with mechanical reset
Data sheet H72181
Instruction H72181

Set-point adjustment internal
Sensor technology capillary tube, remote sensor
Sensor material 1.4435/316L
Protection IP66
Output micro switch
Electrical connection terminal screw
Capillary tube length [m] 2

Areas with gas explosion hazards EX II 2 G Ex de IIC T6
Areas with dust explosion hazards EX II 2 D Ex tD A21 IP 66 T80°C

Type Sensor material Range T
[°C]
Operating
 temperature
[°C]
Media
Temperature
[°C]
KTSB 150S 1.4435/316L 20...150 -50...60 max.165
KTSB 230SS 1.4435/316L 20...230 -50...60 max.250
KTSB 350SS 1.4435/316L 70...350 -50...60 max.380

Product Documentation

H72181_KTSB
Download Data sheet/ Instruction
Download