Trafag Mechanical Thermostats
HVAC ALTEROSTAT, 2 STAGE CONTROLLER M2S...
2 stage controller
internal temperature set-point adjustment
Data sheet H72139
Instruction H70311
Set-point adjustment |
internal |
Sensor technology |
capillary tube, remote sensor |
Sensor material |
Cu,1.4435/316L |
Protection |
IP54 |
Output |
micro switch(2x) |
Electrical connection |
terminal screw |
Operating temperature [°C] |
-30...+70 |
EN 60730-2-9 |
Type 2.B.H. |
Capillary tube length [m] |
2 |
Version with external adjustment on request
Type |
Range T
[°C] |
Switching diff. fixed
[°C] |
Smallest stage diff.
[°C] |
Biggest stage diff.
[°C] |
Media
Temperature
[°C] |
M2S |
35 |
0...35 |
1.8 |
0.8 |
15 |
max.50 |
M2S |
40 |
-5...95 |
2.5 |
1.2 |
35 |
max.105 |
M2S |
95 |
30...40 |
1.8 |
0.8 |
25 |
max.45 |
M2S |
150 |
70...350 |
5 |
2.5 |
80 |
max.380 |
M2S |
230S |
20...230 |
4.5 |
2 |
70 |
max.250 |
M2S |
350S |
20...150 |
3 |
1.5 |
40 |
max.165 |